Home > Products > Thermal Relay > Thermal Relay KORLEN KNR8 TUV Reed Relay 630A

Thermal Relay KORLEN KNR8 TUV Reed Relay 630A

  • $1
    ≥1
    Bag/Bags
Payment Type:
L/C,T/T
Min. Order:
1 Bag/Bags
Transportation:
Ocean,Land,Air
Port:
Ningbo,ShangHai
Share:
  • Product Description
Overview
Product Attributes

Model No.KNR8

BrandKorlen

TheoryThermal Relay

SizeMiniature

Action PrincipleElectronic Type

Protective CharacteristicsOther

LoadMicro Power Relay

Number Of PoleOther

Electricity TypeAc

PhaseOther

UsageLathe Relay

TypeElectric Parameter Relay

Rated Frequency50/60hz

Rated Working Current25;36;93a

StandardsIec947-4;vde0660;gb14048.4

Rated Current0.1-400a

Rated Insulation Voltage660v

Supply Ability & Additional Information

Packagingcarton

Productivity500000PCS/Year

TransportationOcean,Land,Air

Place of OriginWenzhou; Zhejiang; China

CertificateCE;CB;

HS Code8536200000

PortNingbo,ShangHai

Payment TypeL/C,T/T

Packaging & Delivery
Selling Units:
Bag/Bags
Package Type:
carton


Structure feature

●Senies overload relay of thermal metal mode ,tripping class is 10A; 

●Setting current continuous adjustable device;

 ●trip indicator; 

●test button;

●reset button by hand operation and automatic reset button;

●have a pair of No and Nc insulation contact in electricity; 

●mode of installation :install independently or can plug in the AC Contactor



KNR8 series Reed Relay overload relay is suitable for 50Hz/60Hz, rated voltage up 690~1000V,rated current 0.1~400A in main circuit of long time working. It is used to protect AC three-phase asynchronous motor against overload and open phase.

This products Thermal Relay conformity with IEC947-4, VDE0660,GB14048.4 standards . Reed Relay

 Thermal Relay
Latching Relay
Reed Relay
Polarized Relay


Working condifion
●The altituelde should be not higher than 2000m;
●The ambient temperature:-25℃~55℃;
●The relative humidity: when +25℃,the relative humidity of air should be not more than 90%.

 

Feature

●Senies overload relay of thermal metal mode, tripping class is 10A;

●Setting current continuous adjustable device;

●Trip indicator;

●Test button;

●Reset button by hand operation and automatic reset button;

●Have a pair of No and Nc insulation contact in electricity;

●Mode of installation: install independently or can plug in the AC contator.


Thermal Relay
Latching Relay
Reed Relay
Polarized Relay

Parameters & Technical date


Type

Sphere of 
setting 
current(A)

Fuse specification (A)

 

 

IEC947-4

 

 

[1"

[2"

KNR8-50

0.1-0.16

35

0.5

 

0.16-0.25

 

1

 

1.25-0.4

 

1.6

 

0.4-0.63

 

2

 

0.63-1

 

4

 

0.8-1.25

 

4

 

1-1.6

 

6

 

1.25-2

 

6

 

1.6-2.5

 

6

 

2-3.2

 

10

 

2.5-4

 

10

 

3.2-5

 

20

 

4-6.3

 

16

 

5-8

 

16

 

6.3-10

 

25

 

8-12.5

 

25

 

10-14.5

 

25

KNR8-52

0.1-0.16

63

0.5

 

0.16-0.25

 

1

 

0.25-0.4

 

1.6

 

0.4-0.63

 

2

 

0.63-1

 

4

 

0.8-1.25

 

4

 

1-1.6

 

6

 

1.25-2

 

6

 

1.6-2.5

 

6

 

2-3.2

 

10

 

2.5-4

 

10

 

3.2-5

 

16

 

4-6.3

 

16

 

5-8

 

20

 

6.3-10

 

25

 

8-12.5

 

25

 

10-16

 

35

 

12.5-20

 

35

 

16-25

 

50

KNR8-55

1-1.6

100

6

 

1.25-2

 

6

 

1.6-2.5

 

6

 

2-3.2

 

10

 

2.5-4

 

10

 

3.2-5

 

16

 

4-6.3

 

16

 

5-8

 

20

 

6.3-10

 

25

 

8-12.5

 

25

 

10-16

 

35

 

12.5-20

 

50

 

16-25

 

50

 

20-32

 

80

 

25-36

 

80

 

32-40

 

80

 

36-45

 

80

Type

Sphere of 
setting 
current(A)

Fuse specification (A)

 

 

IEC947-4

 

 

[1"

[2"

KNR8-58

12.5-20

160

50

 

16-25

 

50

 

20-32

 

63

 

25-40

 

80

 

32-50

 

100

 

40-57

 

100

 

50-63

 

100

 

57-70

 

125

 

63-80

250

160

 

70-88

 

160

KNR8-60

55-80

250

160

 

63-90

 

160

 

80-110

315

200

 

90-120

 

224

 

110-135

 

224

KNR8-61

55-80

250

160

 

63-90

 

160

 

80-110

315

200

 

90-120

 

224

 

110-135

 

224

 

120-150

 

224

KNR8-59

0.1-0.16

25

0.5

 

0.16-0.25

 

1

 

0.25-0.4

 

1.6

 

0.4-0.63

 

2

 

0.63-1

 

4

 

0.8-1.25

 

4

 

1-1.6

 

6

 

1.25-2

 

6

 

1.6-2.5

 

6

 

2-3.2

 

10

 

2.5-4

 

10

 

3.2-5

 

16

 

4-6.3

 

16

 

5-8

 

16

 

6.3-10

 

16

 

8-12.5

35

25

 

10-16

63

35

 

12.5-20

63

50

 

16-25

63

50

 

20-32

80

63

 

25-40

125

80

 

32-40

160

100

 

40-57

160

125

 

50-63

160

125

KNR8-62

55-80

250 
250

160

 

63-90

 

160

 

80-110

250

200

 

90-120 
110-135 
120-150

315

224

 

135-160 
150-180

355

 

KNR8-66

80-125

500

250

 

125-200

 

315

 

160-250

 

400

 

200-320

 

400

 

250-400

800

500








KORLEN-KNR8KORLEN-KNR8

KORLEN-KNR8KORLEN-KNR8KORLEN-KNR8


KORLEN-KNR8


The company has well experienced workforce, ranging from senior engineers and technicians to factory workers which constitutes a total population of 1,500 workers.  The company covers an area of more than 50 acres of land. Construction site is more than 38000 square meters of the modern industrial zone. Korlen is equipped with modern sophisticated laboratory with high standard examination equipment. Due to our strict compliance in accordance with every country`s electric coding system, the company has managed to obtain more than 20 national patents including other accredited international certificates. This makes Korlen a standout in producing electrical protective devices among its competitors.
 






Product Categories : Thermal Relay

Home > Products > Thermal Relay > Thermal Relay KORLEN KNR8 TUV Reed Relay 630A
Email to this supplier
  • *Subject:
  • *To:
    Ms. Chen
  • *Email:
  • *Message:
    Your message must be between 20-8000 characters
Send Inquiry
*
*

Related Products List

Home

Product

Phone

About Us

Inquiry

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

Send